Filtered by vendor Rockwellautomation Subscriptions
Total 302 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2021-27473 1 Rockwellautomation 1 Connected Components Workbench 2025-04-16 6.1 Medium
Rockwell Automation Connected Components Workbench v12.00.00 and prior does not sanitize paths specified within the .ccwarc archive file during extraction. This type of vulnerability is also commonly referred to as a Zip Slip. A local, authenticated attacker can create a malicious .ccwarc archive file that, when opened by Connected Components Workbench, will allow the attacker to gain the privileges of the software. If the software is running at SYSTEM level, the attacker will gain admin level privileges. User interaction is required for this exploit to be successful.
CVE-2021-27476 1 Rockwellautomation 1 Factorytalk Assetcentre 2025-04-16 10 Critical
A vulnerability exists in the SaveConfigFile function of the RACompare Service, which may allow for OS command injection. This vulnerability may allow a remote, unauthenticated attacker to execute arbitrary commands in Rockwell Automation FactoryTalk AssetCentre v10.00 and earlier.
CVE-2022-1018 1 Rockwellautomation 3 Connected Components Workbench, Isagraf, Safety Instrumented Systems Workstation 2025-04-16 5.5 Medium
When opening a malicious solution file provided by an attacker, the application suffers from an XML external entity vulnerability due to an unsafe call within a dynamic link library file. An attacker could exploit this to pass data from local files to a remote web server, leading to a loss of confidentiality.
CVE-2022-1161 1 Rockwellautomation 48 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 45 more 2025-04-16 10 Critical
An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other.
CVE-2022-1797 1 Rockwellautomation 18 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 15 more 2025-04-16 6.8 Medium
A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online.
CVE-2022-2179 1 Rockwellautomation 4 Micrologix 1100, Micrologix 1100 Firmware, Micrologix 1400 and 1 more 2025-04-16 6.5 Medium
The X-Frame-Options header in Rockwell Automation MicroLogix 1100/1400 Versions 21.007 and prior is not configured in the HTTP response, which could allow clickjacking attacks.
CVE-2022-2463 1 Rockwellautomation 1 Isagraf Workbench 2025-04-16 6.1 Medium
Rockwell Automation ISaGRAF Workbench software versions 6.0 through 6.6.9 are affected by a Path Traversal vulnerability. A crafted malicious .7z exchange file may allow an attacker to gain the privileges of the ISaGRAF Workbench software when opened. If the software is running at the SYSTEM level, then the attacker will gain admin level privileges. User interaction is required for this exploit to be successful.
CVE-2022-3157 1 Rockwellautomation 12 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 9 more 2025-04-16 8.6 High
A vulnerability exists in the Rockwell Automation controllers that allows a malformed CIP request to cause a major non-recoverable fault (MNRF) and a denial-of-service condition (DOS).
CVE-2022-3752 1 Rockwellautomation 10 Compact Guardlogix 5380, Compact Guardlogix 5380 Firmware, Compactlogix 5380 and 7 more 2025-04-16 8.6 High
An unauthorized user could use a specially crafted sequence of Ethernet/IP messages, combined with heavy traffic loading to cause a denial-of-service condition in Rockwell Automation Logix controllers resulting in a major non-recoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online and continue normal operation.
CVE-2024-11155 1 Rockwellautomation 1 Arena 2025-04-14 7.8 High
A “use after free” code execution vulnerability exists in the Rockwell Automation Arena® that could allow a threat actor to craft a DOE file and force the software to use a resource that was already used. If exploited, a threat actor could leverage this vulnerability to execute arbitrary code. To exploit this vulnerability, a legitimate user must execute the malicious code crafted by the threat actor.
CVE-2015-6490 1 Rockwellautomation 2 Micrologix 1100 Firmware, Micrologix 1400 Firmware 2025-04-12 N/A
Stack-based buffer overflow on Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices through B FRN 15.003 allows remote attackers to execute arbitrary code via unspecified vectors.
CVE-2015-6488 1 Rockwellautomation 2 Micrologix 1100 Firmware, Micrologix 1400 Firmware 2025-04-12 N/A
Cross-site scripting (XSS) vulnerability in the web server on Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices before B FRN 15.003 allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.
CVE-2015-6486 1 Rockwellautomation 2 Micrologix 1100 Firmware, Micrologix 1400 Firmware 2025-04-12 N/A
SQL injection vulnerability on Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices before B FRN 15.003 allows remote authenticated users to execute arbitrary SQL commands via unspecified vectors.
CVE-2015-1010 1 Rockwellautomation 1 Rsview32 2025-04-12 N/A
Rockwell Automation RSView32 7.60.00 (aka CPR9 SR4) and earlier does not properly encrypt credentials, which allows local users to obtain sensitive information by reading a file and conducting a decryption attack.
CVE-2014-9209 1 Rockwellautomation 2 Factorytalk Services Platform, Factorytalk View Studio 2025-04-12 N/A
Untrusted search path vulnerability in the Clean Utility application in Rockwell Automation FactoryTalk Services Platform before 2.71.00 and FactoryTalk View Studio 8.00.00 and earlier allows local users to gain privileges via a Trojan horse DLL in an unspecified directory.
CVE-2014-9204 1 Rockwellautomation 1 Rslinx 2025-04-12 N/A
Stack-based buffer overflow in OPCTest.exe in Rockwell Automation RSLinx Classic before 3.73.00 allows remote attackers to execute arbitrary code via a crafted CSV file.
CVE-2014-5424 1 Rockwellautomation 1 Connected Components Workbench 2025-04-12 N/A
Rockwell Automation Connected Components Workbench (CCW) before 7.00.00 allows remote attackers to cause a denial of service (application crash) or possibly execute arbitrary code via an invalid property value to an ActiveX control that was built with an outdated compiler.
CVE-2014-5410 1 Rockwellautomation 1 Ab Micrologix Controller 2025-04-12 N/A
The DNP3 feature on Rockwell Automation Allen-Bradley MicroLogix 1400 1766-Lxxxxx A FRN controllers 7 and earlier and 1400 1766-Lxxxxx B FRN controllers before 15.001 allows remote attackers to cause a denial of service (process disruption) via malformed packets over (1) an Ethernet network or (2) a serial line.
CVE-2016-5814 1 Rockwellautomation 5 Rslogix 500 Professional Edition, Rslogix 500 Standard Edition, Rslogix 500 Starter Edition and 2 more 2025-04-12 N/A
Buffer overflow in Rockwell Automation RSLogix Micro Starter Lite, RSLogix Micro Developer, RSLogix 500 Starter Edition, RSLogix 500 Standard Edition, and RSLogix 500 Professional Edition allows remote attackers to execute arbitrary code via a crafted RSS project file.
CVE-2016-5645 1 Rockwellautomation 6 1766-l32awa, 1766-l32awaa, 1766-l32bwa and 3 more 2025-04-12 N/A
Rockwell Automation MicroLogix 1400 PLC 1766-L32BWA, 1766-L32AWA, 1766-L32BXB, 1766-L32BWAA, 1766-L32AWAA, and 1766-L32BXBA devices have a hardcoded SNMP community, which makes it easier for remote attackers to load arbitrary firmware updates by leveraging knowledge of this community.