Filtered by vendor Siemens Subscriptions
Total 2170 CVE
CVE Vendors Products Updated CVSS v3.1
CVE-2017-12735 1 Siemens 2 Logo\!, Logo\! 8 Bm Firmware 2025-04-20 7.4 High
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). An attacker who performs a Man-in-the-Middle attack between the LOGO! BM and other devices could potentially decrypt and modify network traffic.
CVE-2017-12734 1 Siemens 2 Logo\!8 Bm Fs-05, Logo\!8 Bm Fs-05 Firmware 2025-04-20 7.5 High
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V1.81.2). An attacker with network access to the integrated web server on port 80/tcp could obtain the session ID of an active user session. A user must be logged in to the web interface. Siemens recommends to use the integrated webserver on port 80/tcp only in trusted networks.
CVE-2017-6869 1 Siemens 1 Viewport For Web Office Portal 2025-04-20 N/A
A vulnerability was discovered in Siemens ViewPort for Web Office Portal before revision number 1453 that could allow an unauthenticated remote user to upload arbitrary code and execute it with the permissions of the operating-system user running the web server by sending specially crafted network packets to port 443/TCP or port 80/TCP.
CVE-2017-9944 1 Siemens 2 7kt Pac1200 Data Manager, 7kt Pac1200 Data Manager Firmware 2025-04-20 N/A
A vulnerability has been identified in Siemens 7KT PAC1200 data manager (7KT1260) in all versions < V2.03. The integrated web server (port 80/tcp) of the affected devices could allow an unauthenticated remote attacker to perform administrative operations over the network.
CVE-2017-2685 1 Siemens 3 Sinumerik Integrate Access Mymachine\/ethernet, Sinumerik Integrate Operate Client, Sinumerik Operate 2025-04-20 N/A
Siemens SINUMERIK Integrate Operate Clients between 2.0.3.00.016 (including) and 2.0.6 (excluding) and between 3.0.4.00.032 (including) and 3.0.6 (excluding) contain a vulnerability that could allow an attacker to read and manipulate data in TLS sessions while performing a man-in-the-middle (MITM) attack.
CVE-2017-12740 1 Siemens 1 Logo\! Soft Comfort 2025-04-20 N/A
Siemens LOGO! Soft Comfort (All versions before V8.2) lacks integrity verification of software packages downloaded via an unprotected communication channel. This could allow a remote attacker to manipulate the software package while performing a Man-in-the-Middle (MitM) attack.
CVE-2017-5711 3 Asus, Intel, Siemens 394 B150-a, B150-a Firmware, B150-plus and 391 more 2025-04-20 7.8 High
Multiple buffer overflows in Active Management Technology (AMT) in Intel Manageability Engine Firmware 8.x/9.x/10.x/11.0/11.5/11.6/11.7/11.10/11.20 allow attacker with local access to the system to execute arbitrary code with AMT execution privilege.
CVE-2017-6865 1 Siemens 16 Pcs 7, Primary Setup Tool, Security Configuration Tool and 13 more 2025-04-20 N/A
A vulnerability has been identified in Primary Setup Tool (PST) (All versions < V4.2 HF1), SIMATIC Automation Tool (All versions < V3.0), SIMATIC NET PC-Software (All versions < V14 SP1), SIMATIC PCS 7 V8.1 (All versions), SIMATIC PCS 7 V8.2 (All versions < V8.2 SP1), SIMATIC STEP 7 (TIA Portal) V13 (All versions < V13 SP2), SIMATIC STEP 7 (TIA Portal) V14 (All versions < V14 SP1), SIMATIC STEP 7 V5.X (All versions < V5.6), SIMATIC WinAC RTX 2010 SP2 (All versions), SIMATIC WinAC RTX F 2010 SP2 (All versions), SIMATIC WinCC (TIA Portal) V13 (All versions < V13 SP2), SIMATIC WinCC (TIA Portal) V14 (All versions < V14 SP1), SIMATIC WinCC V7.2 and prior (All versions), SIMATIC WinCC V7.3 (All versions < V7.3 Update 15), SIMATIC WinCC V7.4 (All versions < V7.4 SP1 Upd1), SIMATIC WinCC flexible 2008 (All versions < flexible 2008 SP5), SINAUT ST7CC (All versions installed in conjunction with SIMATIC WinCC < V7.3 Update 15), SINEMA Server (All versions < V14), SINUMERIK 808D Programming Tool (All versions < V4.7 SP4 HF2), SMART PC Access (All versions < V2.3), STEP 7 - Micro/WIN SMART (All versions < V2.3), Security Configuration Tool (SCT) (All versions < V5.0). Specially crafted PROFINET DCP broadcast packets sent to the affected products on a local Ethernet segment (Layer 2) could cause a Denial-of-Service condition of some services. The services require manual restart to recover.
CVE-2016-7987 1 Siemens 8 Eta2 Firmware, Eta4 Firmware, Sicam Ak and 5 more 2025-04-20 N/A
An issue was discovered in Siemens ETA4 firmware (all versions prior to Revision 08) of the SM-2558 extension module for: SICAM AK, SICAM TM 1703, SICAM BC 1703, and SICAM AK 3. Specially crafted packets sent to Port 2404/TCP could cause the affected device to go into defect mode. A cold start might be required to recover the system, a Denial-of-Service Vulnerability.
CVE-2016-8567 1 Siemens 1 Sicam Pas\/pqs 2025-04-20 9.8 Critical
An issue was discovered in Siemens SICAM PAS before 8.00. A factory account with hard-coded passwords is present in the SICAM PAS installations. Attackers might gain privileged access to the database over Port 2638/TCP.
CVE-2016-8566 1 Siemens 1 Sicam Pas\/pqs 2025-04-20 7.8 High
An issue was discovered in Siemens SICAM PAS before 8.00. Because of Storing Passwords in a Recoverable Format, an authenticated local attacker with certain privileges could possibly reconstruct the passwords of users for accessing the database.
CVE-2017-12069 2 Ocpfoundation, Siemens 4 Local Discovery Server, Ua .net, Simatic Pcs7 and 1 more 2025-04-20 N/A
An XXE vulnerability has been identified in OPC Foundation UA .NET Sample Code before 2017-03-21 and Local Discovery Server (LDS) before 1.03.367. Among the affected products are Siemens SIMATIC PCS7 (All versions V8.1 and earlier), SIMATIC WinCC (All versions < V7.4 SP1), SIMATIC WinCC Runtime Professional (All versions < V14 SP1), SIMATIC NET PC Software, and SIMATIC IT Production Suite. By sending specially crafted packets to the OPC Discovery Server at port 4840/tcp, an attacker might cause the system to access various resources chosen by the attacker.
CVE-2017-9947 1 Siemens 8 Apogee Pxc, Apogee Pxc Firmware, Apogee Pxc Modular and 5 more 2025-04-20 5.3 Medium
A vulnerability has been identified in Siemens APOGEE PXC and TALON TC BACnet Automation Controllers in all versions <V3.5. A directory traversal vulnerability could allow a remote attacker with network access to the integrated web server (80/tcp and 443/tcp) to obtain information on the structure of the file system of the affected devices.
CVE-2017-12737 1 Siemens 2 Sm-2556, Sm-2556 Firmware 2025-04-20 N/A
An issue was discovered on Siemens SICAM RTUs SM-2556 COM Modules with the firmware variants ENOS00, ERAC00, ETA2, ETLS00, MODi00, and DNPi00. The integrated web server (port 80/tcp) of the affected devices could allow unauthenticated remote attackers to obtain sensitive device information over the network.
CVE-2017-14491 13 Arista, Arubanetworks, Canonical and 10 more 35 Eos, Arubaos, Ubuntu Linux and 32 more 2025-04-20 9.8 Critical
Heap-based buffer overflow in dnsmasq before 2.78 allows remote attackers to cause a denial of service (crash) or execute arbitrary code via a crafted DNS response.
CVE-2015-7855 4 Debian, Netapp, Ntp and 1 more 11 Debian Linux, Clustered Data Ontap, Data Ontap and 8 more 2025-04-20 6.5 Medium
The decodenetnum function in ntpd in NTP 4.2.x before 4.2.8p4, and 4.3.x before 4.3.77 allows remote attackers to cause a denial of service (assertion failure) via a 6 or mode 7 packet containing a long data value.
CVE-2017-2680 1 Siemens 183 S110 Pn, Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware and 180 more 2025-04-20 6.5 Medium
Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected.
CVE-2017-9938 1 Siemens 1 Simatic Logon 2025-04-20 N/A
A vulnerability was discovered in Siemens SIMATIC Logon (All versions before V1.6) that could allow specially crafted packets sent to the SIMATIC Logon Remote Access service on port 16389/tcp to cause a Denial-of-Service condition. The service restarts automatically.
CVE-2017-9940 1 Siemens 1 Sipass Integrated 2025-04-20 N/A
A vulnerability was discovered in Siemens SiPass integrated (All versions before V2.70) that could allow an attacker with access to a low-privileged user account to read or write files on the file system of the SiPass integrated server over the network.
CVE-2017-9945 1 Siemens 2 7km Pac Switched Ethernet Profinet Expansion Module, 7km Pac Switched Ethernet Profinet Expansion Module Firmware 2025-04-20 N/A
In the Siemens 7KM PAC Switched Ethernet PROFINET expansion module (All versions < V2.1.3), a Denial-of-Service condition could be induced by a specially crafted PROFINET DCP packet sent as a local Ethernet (Layer 2) broadcast. The affected component requires a manual restart via the main device to recover.