Filtered by vendor Siemens
Subscriptions
Total
1936 CVE
CVE | Vendors | Products | Updated | CVSS v3.1 |
---|---|---|---|---|
CVE-2013-0672 | 1 Siemens | 1 Wincc Tia Portal | 2025-04-11 | N/A |
Cross-site scripting (XSS) vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to inject arbitrary web script or HTML via unspecified data. | ||||
CVE-2013-0671 | 1 Siemens | 1 Wincc Tia Portal | 2025-04-11 | N/A |
Directory traversal vulnerability in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to read HMI web-application source code and user-defined scripts via a crafted URL. | ||||
CVE-2011-4530 | 1 Siemens | 1 Automation License Manager | 2025-04-11 | N/A |
Siemens Automation License Manager (ALM) 4.0 through 5.1+SP1+Upd1 does not properly copy fields obtained from clients, which allows remote attackers to cause a denial of service (exception and daemon crash) via long fields, as demonstrated by fields to the (1) open_session->workstation->NAME or (2) grant->VERSION function. | ||||
CVE-2013-0670 | 1 Siemens | 1 Wincc Tia Portal | 2025-04-11 | N/A |
CRLF injection vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote attackers to inject arbitrary HTTP headers and conduct HTTP response splitting attacks via a crafted URL. | ||||
CVE-2013-0669 | 1 Siemens | 1 Wincc Tia Portal | 2025-04-11 | N/A |
The HMI web application in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to cause a denial of service (daemon crash) via a crafted HTTP request. | ||||
CVE-2011-4529 | 1 Siemens | 1 Automation License Manager | 2025-04-11 | N/A |
Multiple buffer overflows in Siemens Automation License Manager (ALM) 4.0 through 5.1+SP1+Upd1 allow remote attackers to execute arbitrary code via a long serialid field in an _licensekey command, as demonstrated by the (1) check_licensekey or (2) read_licensekey command. | ||||
CVE-2013-0668 | 1 Siemens | 1 Wincc Tia Portal | 2025-04-11 | N/A |
Multiple cross-site scripting (XSS) vulnerabilities in the HMI web application in Siemens WinCC (TIA Portal) 11 allow remote attackers to inject arbitrary web script or HTML via a crafted URL. | ||||
CVE-2013-0667 | 1 Siemens | 1 Wincc Tia Portal | 2025-04-11 | N/A |
Cross-site scripting (XSS) vulnerability in the HMI web application in Siemens WinCC (TIA Portal) 11 allows remote attackers to inject arbitrary web script or HTML via a crafted URL. | ||||
CVE-2011-4515 | 1 Siemens | 1 Wincc Tia Portal | 2025-04-11 | N/A |
Siemens WinCC (TIA Portal) 11 uses a reversible algorithm for storing HMI web-application passwords in world-readable and world-writable files, which allows local users to obtain sensitive information by leveraging (1) physical access or (2) Sm@rt Server access. | ||||
CVE-2013-0659 | 1 Siemens | 4 Cp 1604, Cp 1604 Firmware, Cp 1616 and 1 more | 2025-04-11 | N/A |
The debugging feature on the Siemens CP 1604 and CP 1616 interface cards with firmware before 2.5.2 allows remote attackers to execute arbitrary code via a crafted packet to UDP port 17185. | ||||
CVE-2013-0656 | 1 Siemens | 2 Simatic Rf-manager, Simatic Rf-manager 2008 | 2025-04-11 | N/A |
Buffer overflow in a third-party ActiveX component in Siemens SIMATIC RF-MANAGER 2008, and RF-MANAGER Basic 3.0 and earlier, allows remote attackers to execute arbitrary code via a crafted web site. | ||||
CVE-2011-4514 | 1 Siemens | 5 Simatic Hmi Panels, Wincc, Wincc Flexible and 2 more | 2025-04-11 | N/A |
The TELNET daemon in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime does not perform authentication, which makes it easier for remote attackers to obtain access via a TCP session. | ||||
CVE-2012-5409 | 1 Siemens | 1 Sipass Integrated | 2025-04-11 | N/A |
AscoServer.exe in the server in Siemens SiPass integrated MP2.6 and earlier does not properly handle IOCP RPC messages received over an Ethernet network, which allows remote attackers to write data to any memory location and consequently execute arbitrary code via crafted messages, as demonstrated by an arbitrary pointer dereference attack or a buffer overflow attack. | ||||
CVE-2012-4698 | 1 Siemens | 4 Ros, Rox I Os, Rox Ii Os and 1 more | 2025-04-11 | N/A |
Siemens RuggedCom Rugged Operating System (ROS) before 3.12, ROX I OS through 1.14.5, ROX II OS through 2.3.0, and RuggedMax OS through 4.2.1.4621.22 use hardcoded private keys for SSL and SSH communication, which makes it easier for man-in-the-middle attackers to spoof servers and decrypt network traffic by leveraging the availability of these keys within ROS files at all customer installations. | ||||
CVE-2011-4513 | 1 Siemens | 5 Simatic Hmi Panels, Wincc, Wincc Flexible and 2 more | 2025-04-11 | N/A |
Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allow user-assisted remote attackers to execute arbitrary code via a crafted project file, related to the HMI web server and runtime loader. | ||||
CVE-2012-4693 | 2 Invensys, Siemens | 2 Wonderware Intouch, Processsuite | 2025-04-11 | N/A |
Invensys Wonderware InTouch 2012 R2 and earlier and Siemens ProcessSuite use a weak encryption algorithm for data in Ps_security.ini, which makes it easier for local users to discover passwords by reading this file. | ||||
CVE-2012-4691 | 1 Siemens | 1 Automation License Manager | 2025-04-11 | N/A |
Memory leak in Siemens Automation License Manager (ALM) 4.x and 5.x before 5.2 allows remote attackers to cause a denial of service (memory consumption) via crafted packets. | ||||
CVE-2011-4512 | 1 Siemens | 5 Simatic Hmi Panels, Wincc, Wincc Flexible and 2 more | 2025-04-11 | N/A |
CRLF injection vulnerability in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to inject arbitrary HTTP headers and conduct HTTP response splitting attacks via unspecified vectors. | ||||
CVE-2012-3040 | 1 Siemens | 18 Simatic S7-1200, Simatic S7-1200 Cpu 1211c, Simatic S7-1200 Cpu 1211c Firmware and 15 more | 2025-04-11 | N/A |
Cross-site scripting (XSS) vulnerability in the web server on Siemens SIMATIC S7-1200 PLCs 2.x through 3.0.1 allows remote attackers to inject arbitrary web script or HTML via a crafted URI. | ||||
CVE-2012-3037 | 1 Siemens | 18 Simatic S7-1200, Simatic S7-1200 Cpu 1211c, Simatic S7-1200 Cpu 1211c Firmware and 15 more | 2025-04-11 | N/A |
The Siemens SIMATIC S7-1200 2.x PLC does not properly protect the private key of the SIMATIC CONTROLLER Certification Authority certificate, which allows remote attackers to spoof the S7-1200 web server by using this key to create a forged certificate. |