CVE-2021-22774 1 Schneider-electric 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more 2024-11-21 7.5 High
A CWE-759: Use of a One-Way Hash without a Salt vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could lead an attacker to get knowledge of charging station user account credentials using dictionary attacks techniques.
CVE-2021-22773 1 Schneider-electric 12 Evlink City Evc1s22p4, Evlink City Evc1s22p4 Firmware, Evlink City Evc1s7p4 and 9 more 2024-11-21 6.5 Medium
A CWE-620: Unverified Password Change vulnerability exists in EVlink City (EVC1S22P4 / EVC1S7P4 all versions prior to R8 V3.4.0.1), EVlink Parking (EVW2 / EVF2 / EV.2 all versions prior to R8 V3.4.0.1), and EVlink Smart Wallbox (EVB1A all versions prior to R8 V3.4.0.1 ) that could allow an attacker connected to the charging station web server to modify the password of a user.
CVE-2021-22772 1 Schneider-electric 6 T200e, T200e Firmware, T200i and 3 more 2024-11-21 9.8 Critical
A CWE-306: Missing Authentication for Critical Function vulnerability exists in Easergy T200 ((Modbus) SC2-04MOD-07000100 and earlier), Easergy T200 ((IEC104) SC2-04IEC-07000100 and earlier), and Easergy T200 ((DNP3) SC2-04DNP-07000102 and earlier) that could cause unauthorized operation when authentication is bypassed.
CVE-2021-22771 1 Schneider-electric 2 Easergy T300, Easergy T300 Firmware 2024-11-21 7.3 High
A CWE-1236: Improper Neutralization of Formula Elements in a CSV File vulnerability exists in Easergy T300 with firmware V2.7.1 and older that would allow arbitrary command execution.
CVE-2021-22770 1 Schneider-electric 2 Easergy T300, Easergy T300 Firmware 2024-11-21 6.5 Medium
A CWE-200: Information Exposure vulnerability exists in Easergy T300 with firmware V2.7.1 and older that exposes sensitive information to an actor not explicitly authorized to have access to that information.
CVE-2021-22769 1 Schneider-electric 2 Easergy T300, Easergy T300 Firmware 2024-11-21 4.3 Medium
A CWE-552: Files or Directories Accessible to External Parties vulnerability exists in Easergy T300 with firmware V2.7.1 and older that could expose files or directory content when access from an attacker is not restricted or incorrectly restricted.
CVE-2021-22768 1 Schneider-electric 4 Powerlogic Egx100, Powerlogic Egx100 Firmware, Powerlogic Egx300 and 1 more 2024-11-21 9.8 Critical
A CWE-20: Improper Input Validation vulnerability exists in PowerLogic EGX100 (Versions 3.0.0 and newer) and PowerLogic EGX300 (All Versions) that could cause denial of service or remote code execution via a specially crafted HTTP packet.This CVE ID is unique from CVE-2021-22767
CVE-2021-22767 1 Schneider-electric 4 Powerlogic Egx100, Powerlogic Egx100 Firmware, Powerlogic Egx300 and 1 more 2024-11-21 9.8 Critical
A CWE-20: Improper Input Validation vulnerability exists in PowerLogic EGX100 (Versions 3.0.0 and newer) and PowerLogic EGX300 (All Versions) that could cause denial of service or remote code execution via a specially crafted HTTP packet.This CVE ID is unique from CVE-2021-2276
CVE-2021-22766 1 Schneider-electric 4 Powerlogic Egx100, Powerlogic Egx100 Firmware, Powerlogic Egx300 and 1 more 2024-11-21 7.5 High
A CWE-20: Improper Input Validation vulnerability exists in PowerLogic EGX100 (Versions 3.0.0 and newer) and PowerLogic EGX300 (All Versions) that could cause denial of service via a specially crafted HTTP packet
CVE-2021-22765 1 Schneider-electric 4 Powerlogic Egx100, Powerlogic Egx100 Firmware, Powerlogic Egx300 and 1 more 2024-11-21 9.8 Critical
A CWE-20: Improper Input Validation vulnerability exists in PowerLogic EGX100 (Versions 3.0.0 and newer) and PowerLogic EGX300 (All Versions) that could cause denial of service or remote code execution via a specially crafted HTTP packet
CVE-2021-22762 1 Schneider-electric 1 Interactive Graphical Scada System 2024-11-21 7.8 High
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory vulnerability exists inIGSS Definition (Def.exe) V15.0.0.21140 and prior that could result in remote code execution, when a malicious CGF or WSP file is being parsed by IGSS Definition.
CVE-2021-22761 1 Schneider-electric 1 Interactive Graphical Scada System 2024-11-21 7.8 High
A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists inIGSS Definition (Def.exe) V15.0.0.21140 and prior that could result in disclosure of information or remote code e+F15xecution due to missing length check on user supplied data, when a malicious CGF file is imported to IGSS Definition.
CVE-2021-22760 1 Schneider-electric 1 Interactive Graphical Scada System 2024-11-21 7.8 High
A CWE-763: Release of invalid pointer or reference vulnerability exists inIGSS Definition (Def.exe) V15.0.0.21140 and prior that could result in loss of data or remote code execution due to missing checks of user-supplied input data, when a malicious CGF file is imported to IGSS Definition.
CVE-2021-22759 1 Schneider-electric 1 Interactive Graphical Scada System 2024-11-21 7.8 High
A CWE-416: Use after free vulnerability exists inIGSS Definition (Def.exe) V15.0.0.21140 and prior that could result in loss of data or remote code execution due to use of unchecked input data, when a malicious CGF file is imported to IGSS Definition.
CVE-2021-22758 1 Schneider-electric 1 Interactive Graphical Scada System 2024-11-21 7.8 High
A CWE-824: Access of uninitialized pointer vulnerability exists inIGSS Definition (Def.exe) V15.0.0.21140 and prior that could result in loss of data or remote code execution due to lack validation of user-supplied input data, when a malicious CGF file is imported to IGSS Definition.
CVE-2021-22757 1 Schneider-electric 1 Interactive Graphical Scada System 2024-11-21 7.8 High
A CWE-125: Out-of-bounds read vulnerability exists inIGSS Definition (Def.exe) V15.0.0.21140 and prior that could result in disclosure of information or remote code execution due to lack of sanity checks on user-supplied input data, when a malicious CGF file is imported to IGSS Definition.
CVE-2021-22756 1 Schneider-electric 1 Interactive Graphical Scada System 2024-11-21 7.8 High
A CWE-125: Out-of-bounds read vulnerability exists inIGSS Definition (Def.exe) V15.0.0.21140 and prior that could result in disclosure of information or remote code execution due to lack of user-supplied data validation, when a malicious CGF file is imported to IGSS Definition.
CVE-2021-22755 1 Schneider-electric 1 Interactive Graphical Scada System 2024-11-21 7.8 High
A CWE-787: Out-of-bounds write vulnerability exists inIGSS Definition (Def.exe) V15.0.0.21140 and prior that could result in disclosure of information or remote code execution due to lack of sanity checks on user-supplied data, when a malicious CGF file is imported to IGSS Definition.
CVE-2021-22754 1 Schneider-electric 1 Interactive Graphical Scada System 2024-11-21 7.8 High
A CWE-787: Out-of-bounds write vulnerability exists inIGSS Definition (Def.exe) V15.0.0.21140 and prior that could result in loss of data or remote code execution due to lack of proper validation of user-supplied data, when a malicious CGF file is imported to IGSS Definition.
CVE-2021-22753 1 Schneider-electric 1 Interactive Graphical Scada System 2024-11-21 7.8 High
A CWE-125: Out-of-bounds read vulnerability exists inIGSS Definition (Def.exe) V15.0.0.21140 and prior that could result in loss of data or remote code execution due to missing length checks, when a malicious WSP file is being parsed by IGSS Definition.